Design of the Optimum Heat Pipe Heat Exchanger to Recover Heat From Flue Gas of Boiler in case of Chiang Mai Orchid Hotel, Thailand
Email tác giả liên hệ:
ypracha@rmutl.ac.thDOI:
https://doi.org/10.54644/jte.78B.2023.1446Từ khóa:
heat pipe heat exchanger, boiler, greenhouse gas, effectiveness, net savingTóm tắt
This study aims to design the optimum heat pipe heat exchanger (HPHE) to recover heat from flue gas of boiler for increasing the temperature of feed water. The optimum thermosyphon heat exchanger sizing was simulated on the basis of thermo-economical method and simulation program was construct by using the MATLAB 2021b. The program was simulated by input physical parameters of the thermosyphon and heat exchanger and the thermoeconomic parameters. It was found that R134a was chosen as the working fluid of this study. In addition, the optimum of number of tubes, heat transfer rate and the optimized effectiveness of HPHE were 87 tubes, 4,873 W and 0.237, respectively. Moreover, the net saving and payback period of this HPHE were 14,865 USD and 310 days, respectively.
Tải xuống: 0
Tài liệu tham khảo
Collaboration for change (C4C), Office of the Permanent Secretary, Ministry of Energy, Thailand. Annual Report, 2021.
P. Terdtoon , Heat pipe, Department of Mechanical Engineering, Chiang Mai University, Chiang Mai, Thailand, 1993.
M.S. Soylemez, “On the optimum heat exchanger sizing for heat recovery,” Energy Conversion&Manage., vol. 41, pp. 1419-1427, 1999.
M. S. Soylemez, “On the thermoeconomical optimization of Heat Pipe Heat Exchanger HPHE for waste heat recovery,” Energy Conversion&Manage., vol. 44, pp. 2509-2517, 2002.
P. Yeunyongkul, “Optimum design of heat pipe condenser for vapor compression refrigeration,” Ph.D. dissertation, Chiang Mai University, Chiang Mai, Thailand, 2012.
W. Prajumchop, “Thermoeconomical optimization of heat pipe heat exchanger,” M.S. Thesis, Chiang Mai University, Chiang Mai, Thailand, 2005.
ESDU 81038. Heat pipes – performance of two-phase closed thermosyphons, Nov. 1983.
ESDU 80017. Thermophysical properties of heat pipe working fluids: operating range between –60°C and 300°C, Aug. 1980.
Tải xuống
Đã Xuất bản
Cách trích dẫn
Giấy phép
Bản quyền (c) 2023 Tạp chí Khoa học Giáo dục Kỹ Thuật - ĐH SPKT TP.HCM
Tác phẩm này được cấp phép theo Giấy phép quốc tế Creative Commons Attribution-NonCommercial 4.0 .
Bản quyền thuộc về JTE.